301, Building 2, Houhai Industrial Park, Liyuhe Industrial Zone, Loucun Community, Xinhu Street, Guangming District, Shenzhen
Product :All-in-one Off-Grid solarcharger inverter Power Rating :3000W~30kW Input Voltage :1 x 220V/230VAC (1Phase + N) Rated Output Voltage :230vac Output Accuracy :±5% Phase :Single Phase Other voltages or requirements can be customized.
Models |
HF4830S60-145 |
HF4840S80 -145 |
HF4850S80-145 |
HF4825U80 -145 |
HF4830U80 -145 |
HF4835U80-145 |
AC mode |
||||||
Rated input voltage |
220/230Vac |
110/120Vac |
||||
Input voltage range |
(170Vac~280Vac) ±2% |
(90Vac~140Vac) ±2% |
||||
|
|
|
||||
Frequency |
50Hz/ 60Hz (Auto detection) |
|||||
Frequency Range |
47±0.3Hz ~ 55±0.3Hz (50Hz); |
|||||
|
57±0.3Hz ~ 65±0.3Hz (60Hz); |
|||||
Overload/short circuit protection |
Circuit breaker |
|||||
Efficiency |
>95% |
|||||
Conversion time (bypass and inverter) |
10ms (typical) |
|||||
AC reverse protection |
Available |
|||||
Maximum bypass overload current |
30A |
40A |
||||
Inverter mode |
||||||
Output voltage waveform |
Pure sine wave |
|||||
Rated output power (VA) |
3000 |
4000 |
5000 |
2500 |
3000 |
3500 |
Rated output power (W) |
3000 |
4000 |
5000 |
2500 |
3000 |
3500 |
Power factor |
1 |
|||||
Rated output voltage (Vac) |
230Vac |
120Vac |
||||
Output voltage error |
±5% |
|||||
Output frequency range (Hz) |
50Hz ± 0.3Hz |
|||||
|
60Hz ± 0.3Hz |
|||||
Maximum Efficiency |
>92% |
>91% |
||||
Overload protection |
(102% < load <125%) ±10%: report error and turn off the output after 5 minutes; |
(102% < load <110%) ±10%: report error and turn off the output after 5 minutes; |
||||
|
(125% < load < 150%) ± 10%: report error and turn off the output after 10 seconds; |
(110% < load < 125%) ± 10%: report error and turn off the output after 10 seconds; |
||||
|
Load >150% ±10%: report error and turn off the output after 5 seconds; |
(Load >125% ±10%): report error and turn off the output after 5 seconds; |
||||
Peak power |
6000VA |
8000VA |
10000VA |
4000VA |
4500VA |
5000VA |
Loaded motor capability |
2HP |
3HP |
4PH |
1HP |
2HP |
2HP |
|
|
|
|
|
|
|
Rated battery input voltage |
48V (Minimum starting voltage 44V) |
|||||
Battery voltage range |
Undervoltage alarm/shutdown voltage/overvoltage alarm /overvoltage recovery... settable on LCD screen) |
|||||
|
|
|||||
Power saving mode self-consumption |
Load≤50W |
|||||
AC charging |
||||||
Battery type |
Lead acid or lithium battery |
|||||
Maximum charge current(can be set) |
0-60A |
0-40A |
||||
Charge current error |
± 5Adc |
|||||
Charge voltage range |
40 –58Vdc |
40 –60Vdc |
||||
Short circuit protection |
Circuit breaker and blown fuse |
|||||
Circuit breaker specifications |
30A |
40A |
||||
Overcharge protection |
Alarm and turn off charging after 1 minute |
|||||
PV charging |
||||||
Maximum PV open circuit voltage |
145Vdc |
|||||
PV operating voltage range |
60-145Vdc |
|||||
MPPT voltage range |
60-115Vdc |
|||||
Battery voltage range |
40-60Vdc |
|||||
Maximum output power |
3200W |
4200W |
||||
PV charging current range (can be set) |
0-60A |
0-80A |
||||
Charging short circuit protection |
Blown fuse |
|||||
Wiring protection |
Reverse polarity protection |
|||||
Hybrid charging Max charger current specifications (AC charger+PV charger) |
||||||
Max charger current(can be set) |
0-120A |
0-140A |
0-120A |
|||
Certified specifications |
||||||
Certification |
CE(EN62109-1) |
CE(EN62109-1)/ETL(UL 1741) |
||||
EMC certification level |
EN61000, C2 |
|||||
Operating temperature range |
-15°C to 55°C |
|||||
Storage temperature range |
-25°C ~ 60°C |
|||||
Humidity range |
5% to 95% (Conformal coating protection) |
|||||
Noise |
≤60dB |
|||||
Heat dissipation |
Forced air cooling, variable speed of fan |
|||||
Communication interface |
USB/RS485(WiFi/GPRS)/Dry node control |
|||||
Size mm |
378*280*103 |
426*322*124 |
||||
(L*W*D) |
|
|
||||
Weight (kg) |
6.2 |
10.8 |