301, Building 2, Houhai Industrial Park, Liyuhe Industrial Zone, Loucun Community, Xinhu Street, Guangming District, Shenzhen
Product : Low Frequency Transformer-based Double-conversion Online UPS Model : WLF-33 (10kVA-600kVA) Input Voltage : 3 x 380VAC (3Phase + N) (Can Customized) Input Range : 285V-475VAC Output Voltage : 3 x 380VAC (3Phase + N) (Can Customized) Output Accuracy : ±1% Phase : Three Phase
WLF series three-in three-output low frequency double conversion online intelligent fully digital UPS is a sine wave online product that integrates digitalization, informatization and networking. It has a powerful information collection system, signal processing system and complete protection system. It is used in various power consumption environments. It has good personalized design and friendly human-computer dialogue functions. It uses advanced all-digital technology to protect the safety of computers, communication instruments, electrical facilities, medical and other electrical equipment, and comprehensively solve the problem of power outages, voltage fluctuations/sudden changes, frequency changes, electronic noise, lightning strikes and other electrical problems.
•Digital control to achieve online double conversion
•Built-in output isolation transformer
•Industrial design for a variety of harsh conditions
•Front maintenance design
•Adapt to all kind of load.
•Can be up to 4 parallel operation
•Rich communication interface
•Friendly and Intuitive User Interface. Large Color Touch LCD Screen with multi-functional buttons. Safe and Reliable
•90% of system components are from international famous brands. All devices will be aged and tested for more than 24 hours
WLF Three Phase Low Frequency Double-Conversion Online UPS |
|||||||||||
Power Rating |
10KVA/ 8KW |
15KVA/ 12KW |
20KVA/ 16KW |
30KVA/ 24KW |
40KVA/ 32KW |
60KVA/ 48KW |
80KVA/64KW |
100KVA/ 80KW |
120KVA/ 96KW |
160KVA/ 128KW |
200KVA/ 160KW |
Mains Input |
|||||||||||
Rated Voltage |
3 x 380VAC/400VAC/415VAC (3Phase + N) |
||||||||||
Voltage Range/Window |
± 25%VAC |
||||||||||
Frequency |
50/60 Hz ± 10 % |
||||||||||
Bypass Input |
|||||||||||
Rated Voltage |
3 x 380VAC/400VAC/415VAC (3Phase + N) |
||||||||||
Voltage Range/Window |
+10%, +15%, +20% (can be set); -10%, -20%, -30% (can be set) |
||||||||||
Frequency |
±2% (±0.5%, +1%, ±2%, ±3% can be set) |
||||||||||
Output |
|||||||||||
Output Voltage |
3 x 380VAC/400VAC/415VAC (3phase + N) |
||||||||||
Voltage Accuracy |
Static: ±1% Typical value |
||||||||||
Frequency(Synchronization correction range) |
50/60 Hz synchronize ±1 % |
||||||||||
Frequency Tracking Rate |
±1 Hz/s |
||||||||||
Output Waveform |
Pure Sine Wave |
||||||||||
TotalHarmonic(THDv) |
<2% (Linear Load) ; <5% (Nonlinear Load) |
||||||||||
Phase Unbalance |
120º ±1% (Balance Load) ; 120º ±2% (50% Unbalance Load) |
||||||||||
Time for adjustion (Dynamically) |
3 cycles returned to rated 90% |
||||||||||
Overload Capacity |
110%~ 150% 10minutes~1 minute;150%~ 160% >1 minute~200ms;200ms for>160% |
||||||||||
Peak Factor |
3:1 |
||||||||||
Load Power Factor Range |
0.6~1 (Capacitive or Inductive) |
||||||||||
Unbalanced output voltage @ 100% unbalanced load |
<1% |
||||||||||
Current Limit |
Very heavy overload, short circuit: voltage RMS limit; impulse current: peak voltage limit |
||||||||||
Efficiency |
91% |
91% |
92% |
93% |
|||||||
Bypass |
|||||||||||
Type |
Static Switch |
||||||||||
Voltage |
3 x 380VAC/400VAC/415VAC (3Ph + N) |
||||||||||
Frequency |
50/60 Hz |
||||||||||
Control Way |
Microprocessor Control |
||||||||||
Inverter to bypass switching time |
Synchronous mode - switching uninterrupted, asynchronous mode - 10ms |
||||||||||
Overload Capacity |
150%~ 180% 1h~1s;180%~ 200%30s~200ms;200ms for>200% |
||||||||||
Switch to Bypass |
Overload larger than 160% would be switched immediately |
||||||||||
Switch back to the inverter |
The alarm is switched automatically after alarm clearing |
||||||||||
Maintenance Bypass |
|||||||||||
Type |
uninterrupted |
||||||||||
Voltage |
3 x 400V (3 Phase+ N) |
||||||||||
Frequency |
50/60 Hz |
||||||||||
Battery & Charging |
|||||||||||
Battery Number(12V) |
Standard is 32pcs; 29/30/32(Adjustable) |
||||||||||
Charging Mode |
Option: constant voltage charging / constant current charging |
||||||||||
Charge Current |
Default 10A, maximum 40A |
||||||||||
Battery Type and Quantity |
Sealed lead-acid batteries, nickel cadmium battery |
||||||||||
Physical Performance |
|||||||||||
Size,WxDxH(mm) |
300*600*810 |
400*750*1010 |
450*830*1160 |
700*800*1500 |
700*800*1700 |
||||||
Net Weight (KG ) (Without batteries) |
118 |
120 |
145 |
193 |
278 |
365 |
471 |
573 |
650 |
785 |
840 |
Product specifications are subject to us. If any changes, there would be no notice. |
No |
Model |
Power Rating |
Description |
Product Size (mm) |
Gross Weight (KG) |
1 |
WLF33-10K |
8KW |
Input Voltage: |
300*600*810 |
118 |
2 |
WLF33-15K |
12KW |
120 |
||
3 |
WLF33-20K |
16KW |
145 |
||
4 |
WLF33-30K |
24KW |
193 |
||
5 |
WLF33-40K |
32KW |
400*750*1010 |
278 |
|
6 |
WLF33-60K |
48KW |
365 |
||
7 |
WLF33-80K |
64KW |
450*830*1160 |
471 |
|
8 |
WLF33-100K |
80KW |
573 |
||
9 |
WLF33-120K |
96KW |
700*800*1500 |
650 |
|
10 |
WLF33-160K |
128KW |
700*800*1700 |
785 |
|
11 |
WLF33-200K |
160KW |
840 |
||
12 |
WLF33-300K |
240KW |
1035*840*1800 |
2200 |
|
11 |
WLF33-400K |
320KW |
|
1200*1000*1800 |
2700 |
12 |
WLF33-500K |
400KW |
|
1400*1000*1800 |
3200 |
1. The above Sizes and Weights are our standard type for your information. |
|||||
2. Customized products maybe with different sizes and weights. |
|||||
3. Product specifications are subject to change without further notice. |
★ Industrial application protection
★ Traffic, power, medical, venues and other important institutions power protection
★ Small data room
★ Communication network management center
★ Office automation
★ Experimental instruments and equipment
etc.