Model | JLF-3310 | JLF-3315 | JLF-3320 | JLF-3330 | JLF-3340 | JLF-3360 | JLF-3380 | JLF-33100 | JLF-33120 | JLF-33160 | JLF-33200 |
Capacity | 10KVA 9KW | 15KVA 13.5KW | 20KVA 18KW | 30KVA 27KW | 40KVA 32KW | 60KVA 54KW | 80KVA 72KW | 100KVA 90KW | 120KVA 108KW | 160KVA 144KW | 200KVA 180KW |
Host Machine Specification |
UPS Structure | Online Double Conversion |
Appearance | Low Frequency with Output Isolated Transformer |
Overall Efficiency (AC-AC) | 90% |
Noise (In 2 Meters) | < 50-60dB |
Working Temp. | -10-40℃ |
Storage Temp. | -25 ~ 60℃ (Without Batteries) |
Humidity | < 95%, Non-Condensing |
National Standard | EN50091-1/IEC950 |
International Standard | EN 50091-1/2; EN62040-1; EN62040-2 |
Parallel Redundancy | Available upto 8 units |
Protection | Overload, Short-Circuit, Over Temp., Utility Power Voltage High/low, BAT Voltage High/low |
ECO | Available |
EPO Function | Available |
DC Start | Available (Not Recommended) |
Generator Compatibility | Available |
Display | 5-7 inch LCD color touch screen + LED working indicators including Input/Output Voltage, Frequency, Current, Power, Load Capacity, Serial Number, Operational Mode, Discharge Time, History Logs. All settings including can be done on the front panel, including battery voltage, input and output voltage, frequency, parallel setting and etc. |
Mute | Auto |
Cabinet Standard | IP20 |
Cooling System | Intelligent Speed Control Cooling Fan |
Elevation | <1500M, Without Derated |
Rectifier Specification |
Input Voltage | 380Vac+N+W(3 phase + PE) |
Input Voltage Range | 285-475Vac |
Input Frequency Range | 45-65Hz |
Input PF | 0.95( with input filter) |
THDI | <5% (with optional accessories) |
Dual Input Availability | Available(Optional accessories) |
Input Mis Phase Protection | Misphase Alarm, UPS will not be started |
Input Phase lost Protection | Phase Lost Alarm, UPS work on Bypass mode |
Soft-Start | > 20 Seconds |
Input Current | 23A | 31A | 39A | 54A | 70A | 100A | 125A | 160A | 192A | 256A | 320A |
Output Specification |
Output Voltage | Line Voltage: 380×(1±1%)AC or Phase Voltage: 220×(1±1%)AC |
Output PF | 0.8/0.9 (No lag) |
Output Voltage Regulation | 380Vac±1%(Static Load); 380Vac±2%(50-0% Sudden Change); 380Vac±3%(100-0% Sudden Change) |
Output Freq | ±8% at 50Hz: Online Mode tracking input and bypass freq.; ±0.1%: when input or bypass frequency is more than ±8% or under BAT Mode |
THD | < 1%(Linear Full Load),< 3%(Non-Linear Full Load) |
3 Phase Unbalanced | Allow 3 Phase 100% Unbalanced |
Output Volt. Unbalanced | ≤1%(Balanced Load); ≤2%(50% Balanced Load) |
Input/Output Phase Swift | ≤1°(Balanced Load); ≤2°(50% Balanced Load) |
Frequency Tracking Range | 45-65Hz |
Output Waveform | Pure Sine Wave |
Overload | >125%: More than 10 mins; > 150%: More than 60s transfer to bypass |
Crest Ratio | 3∶1 |
Short-Circuit | Circuit Auto-Protection, Bypass Switch Tripping |
Output Abnormal | INV. Output Auto-Locked Protection |
Bypass Specification |
Static Bypass Transfer Time | 0ms |
Static Bypass Input Range | 380Vac(-15~+15%) |
Frequency Range | 50/60Hz±1Hz, ±2Hz, ±3Hz Adjustable |
Bypass --> INV Transfer Time | 2ms |
Frequency Tracking Speed | 0.5-2hz/s |
Manual Maintenance Bypass | Available |
Battery Specification |
Charging Methods | DSP Controlled Charger: Equalized/Pulse Charge, Float Charge, Intelligent Battery Management |
Type | Sealed Lead Acid Maintenance Free |
Rated Volts/Units | 12V/384Vdc, Std. for 32 Units, adjustable from 28-32 units |
Float Charge Voltage | 438Vdc |
Charging Current | Can be set from the front Screen |
Abnormal Protections | BAT over-charged, Emergency charger shutdown protection or UPS shutdown protection |
Communication Specification |
Communication Port | RS232/SNMP/485/Dry Contact(Optional Accessory) |
Remote Software | Multi-functional Monitoring System, Online and BAT Mode Status, BAT Fault, Remote Control |
Physical Parameters |
Size mm(W×H×D) | 475×990×700 | 550×1100×800 | 605×1350×800 | 800×1600×800 | 1100×1850×850 |
Net Weight Kg | 210 | 223 | 230 | 280 | 330 | 450 | 550 | 630 | 750 | 810 | 855 |